| Product classification | Confirm whether the device is an RCCB (residual-current protection only) or an RCBO (residual-current and overcurrent protection). Check rated voltage, current, poles, residual operating current, and intended application. | IEC 61008-1 for RCCBs without integral overcurrent protection; IEC 61009-1 for RCBOs. | Product datasheet, technical drawings, rated-value schedule, and clearly identified model configuration. |
| Design and manufacturing controls | Review control of incoming materials, component traceability, assembly processes, calibrated production equipment, and handling of nonconforming products. | Documented quality-management processes; ISO 9001 certification may support assessment of the manufacturer’s quality system. | Quality-system certificate and scope, process-control records, calibration records, inspection plans, and corrective-action examples. |
| Residual-current operation | Verify that the device trips at the specified residual current and within the required time under applicable test conditions. Check the declared device type and compatibility with the intended waveform. | Applicable requirements and test methods in IEC 61008-1 or IEC 61009-1; device type and rating should match the product documentation. | Type-test reports identifying the exact model, rated values, test conditions, results, and laboratory. |
| Electrical endurance and switching | Assess performance over specified operating cycles and under relevant load and switching conditions. Confirm that test results correspond to the offered product configuration. | Endurance and operating tests specified by the applicable product standard. | Test reports, production inspection records, and documented procedures for monitoring product consistency. |
| Temperature rise and dielectric performance | Check temperature-rise results at declared operating conditions, insulation performance, and dielectric withstand test results. | Applicable electrical and thermal test clauses in IEC 61008-1 or IEC 61009-1. | Laboratory reports showing test setup, rated conditions, acceptance criteria, measured results, and sample identification. |
| Short-circuit and conditional performance | For devices with integral overcurrent protection, review short-circuit test performance. For RCCBs, verify declared conditional short-circuit current and the required upstream protective device conditions. | Applicable short-circuit requirements in IEC 61009-1 or IEC 61008-1, as appropriate. | Test report, declared ratings, coordination information, and any specified backup-protection requirements. |
| Marking and user information | Check that ratings, residual-current characteristics, terminal identification, wiring information, and manufacturer details are legible and consistent with the technical file. | Product-standard marking and documentation requirements; applicable market rules may add further requirements. | Label artwork, installation instructions, packaging details, and a sample product marking review. |
| Certification and market access | Confirm which approvals are required in the destination market and whether certificates cover the exact product family, ratings, and manufacturing site. | Requirements vary by jurisdiction. IEC-based testing does not by itself establish approval for every market; CE marking, where applicable, requires the manufacturer to meet relevant EU legislation and prepare the required documentation. | Current certificates or declarations, certificate scope and validity, supporting test reports, and destination-market compliance documentation. |
| Independent laboratory testing | Assess the competence and independence of the laboratory, the scope of its accreditation, and whether the report identifies the tested samples unambiguously. | ISO/IEC 17025 accreditation is a common benchmark for testing and calibration laboratory competence. | Laboratory accreditation certificate and scope, complete test reports, sample photographs, and report verification details. |
| Ongoing quality and change control | Determine how design, material, component, and production-site changes are reviewed and whether approvals or retesting are required before changes are introduced. | Documented change control and production consistency procedures; certification schemes may impose additional surveillance requirements. | Change-control procedure, revision history, supplier-control records, surveillance records, and batch traceability examples. |