| 1 | Motor output rating | 200 kW | Confirm whether the stated rating is motor shaft output; starter selection is normally based on the motor’s rated current and the application duty. |
| 2 | Supply voltage | 400 V, three-phase | Verify the site’s actual voltage and frequency, and ensure they are within the starter’s specified operating range. |
| 3 | Estimated full-load current at 400 V | Approximately 350–360 A | Illustrative estimate using 95% motor efficiency and 0.85 power factor. Use the motor nameplate current for final sizing. |
| 4 | Current estimate at other voltages | Approximately 376 A at 380 V; approximately 345 A at 415 V | Estimates assume the same 200 kW output, 95% efficiency, and 0.85 power factor. Actual motor current varies by motor design and operating point. |
| 5 | Starting current setting | Often evaluated in the range of 2–4 times motor full-load current | This is an initial application-dependent reference, not a guaranteed setting. Load torque, acceleration time, and supply limits affect the required value. |
| 6 | Starting ramp and acceleration | Set to suit the driven load; no universal ramp time | Check that the motor accelerates reliably without excessive heating or an unnecessarily long start. A soft starter does not provide the same speed control as a variable-frequency drive. |
| 7 | Load and starting duty | Assess load inertia, breakaway torque, starts per hour, and start duration | Frequent starts or heavy-duty starts can require a higher starter rating or additional cooling. Confirm the duty against the device’s published rating and thermal limits. |
| 8 | Bypass arrangement | Check whether an internal or external bypass is required | A bypass contactor typically carries motor current after acceleration, reducing soft-starter power losses during normal running. Follow the selected equipment’s wiring instructions. |
| 9 | Protection and coordination | Check motor overload protection, short-circuit protection, and upstream coordination | Confirm the protection functions provided by the starter and any additional devices required by the system design and applicable electrical rules. |
| 10 | Installation conditions and standards | Verify ambient temperature, enclosure, ventilation, and applicable product standards | Installation conditions can affect permissible current and duty. IEC 60947-4-2 covers semiconductor motor controllers and starters; confirm the applicable edition and local requirements. |